Een installateur gebruikt Extended Coverage sprinklers in een kantoorgebouw. Hij projecteert de sprinklers als volgt.
Er zijn 2 projecteringsregels van toepassing:
Volgens NFPA 13, § 8.4.3. moet het plafond unobstructed, flat en smooth ceiling zijn. Omdat de plafonds voorzien zijn van plafondeilanden is dit niet het geval. Maar.
Volgens NFPA 13,§ 8.8.4.1.2 Obstructed Construction. Under obstructed construction, the sprinkler deflector shall be located in accordance with one of the following arrangements
1. Installed with the deflectors within the horizontal planes of 1 in. to 6 in. (25 mm to 150 mm) below noncombustible structural members and a maximum distance of 22 in. (550 mm) below the ceiling/roof deck.
2. Installed with the deflectors at or above the bottom of noncombustible structural member to a maximum of 22 in. (550 mm) below the noncombustible ceiling/roof deck where the sprinkler is installed in conformance with 8.8.5.1.2
Dilemma Volgens de NFPA-regels klopt de projectie. Maar ik heb toch het idee dat dit niet goed gaat werken omdat de warmte aan de linkerkant van de doorsnede onder het plafondeiland duikt.
Alternatieve analyse Deze situatie niet worden benaderd als een “obstructed ceilingâ€. De classificatie (obstructed of unobstructed) wordt bepaald door de constructie aan het dak en deze zwevende plafonds zijn obstructies onder de dakconstructie.
In de NFPA13 2016 editie zijn er aanvullende richtlijnen opgenomen die aangeven wanneer het toegestaan is geen sprinklers boven (cloud ceilings) zwevende plafonds aan te brengen. Zie onderstaande kopieën afkomstig uit de NFPA13. Dus kleine openingen zijn toegestaan conform paragraaf 8.15.1.2.1.2 en tabel 8.15.24.1.
3.3.5.1 Cloud Ceiling. Any ceiling system installed in the same plane with horizontal openings to the structure above on all sides. This does not include sloped ceilings as defined in 3.3.5.4.
8.15.1.2.1.2 Small openings with a combined total area of not more than 20 percent of the ceiling, construction feature, or plane used to determine the boundaries of the concealed space shall be permitted where length greater than 4 ft (1.2 m) shall not have a width greater than 8 in. (200 mm).
8.15.24 Cloud Ceilings.
8.15.24.1* Sprinklers shall be permitted to be omitted above cloud ceilings where both of the following apply: (1)*The openings around the cloud and the maximum sprinkler protection area meet the requirements of 8.15.1.2.1.2 and Table 8.15.24.1 (2) The requirements of 8.15.24.2 are met.
8.15.24.2 When sprinklers are omitted from above a cloud ceiling in accordance with 8.15.24.1, the requirements of this section shall apply.
8.15.24.2.1 All sprinklers shall be quick response standard spray or extended coverage pendent or upright sprinklers.
8.15.24.2.1.1 Where extended coverage sprinklers are used,the maximum distance between sprinklers shall not exceed 16 ft (4.9 m).
8.15.24.2.2 Maximum cloud ceiling height shall not exceed 20 ft (6.1 m).
8.15.24.2.3 Maximum spacing shall not exceed the maximum requirements of Table 8.6.2.2.1(a) for light hazard and Table 8.6.2.2.1(b) for ordinary hazard.
8.15.24.2.4 Cloud ceilings shall be of smooth ceiling construction.
8.15.24.2.5* For irregular shaped ceiling clouds (not rectangular) the minimum width dimension shall be the smallest width dimension of the cloud and for the gap shall be the greatest dimension between clouds or adjacent walls as applicable.